DC screen features:
The system adopts a unique “one-line access” wiring technology, which greatly facilitates the on-screen wiring of the large-capacity DC system and facilitates user maintenance.
● The natural cooling mode of the charging module greatly improves the average time between failures, and can be used in places where the environment is relatively harsh.
● The charging module can be hot swapped, and the average repair time is greatly reduced.
● Adopting the latest international soft switch technology, the main devices use high-quality brand-name products.
● Battery automatic management and protection, real-time automatic monitoring of the battery's terminal voltage, charge and discharge current, and control the battery's average charge and float charge, with battery over-voltage and charge over-current sound and light alarm.
● The device can be programmed via the public telephone line for remote maintenance diagnosis.
DC screen maintenance and maintenance of the following points:
1.2.1 Sturdy screws.
After six months of equipment operation, all connecting screws should be sturdy, especially the main circuit connecting screws.
1.2.2 Battery Activation (Except for this function)
1.2.3 Repair Replace the high frequency module and JK0403 system.
Pull the high-frequency module and the hot-swap plug on the back of the JK0403 online. Loosen the fastening screws on the module and the JK0403 panel. Pull out the module and the JK0403 from the front.
1.2.5 Replacing the Battery
Use a special puller tool to pull out the two NT00 fuses to separate the battery pack from the system and replace the battery.
1.2.6 DC screen shutdown
Disconnect all DC feed-out switches and disconnect the AC